1-6KW communication inverter
    发布时间: 2024-04-24 17:11    

1-6KW communication inverter

1-6KW communication inverter
TXNB series  rated capacity1kVA2kVA3kVA4kVA5kVA6kVA
AC
input
Rated voltage220Vac
Voltage range175V~265V
Maximum input current3.7A7.2A11A14.5A23A27A
Frequency range45Hz~55Hz
Power factor0.8
DC
input
Rated voltage24V/48V48V
Maximum input current34A/17A66.7A/33A100A/50A133A/67A104A125A
Voltage range21V~30V/42V~60V42V~60V
Mains charging
(optional)
Charging current5A/24V system    5A/48V system10A~60A/48V system
Switching timeAC/DC switching time≤10ms
AC
output
Rated voltage220Vac/230Vac/240Vac
Output voltage range220/230/240Vac:±1%
Rated output currentAC:3.6AAC:7.2AAC:11AAC:14.5AAC:18AAC:22A
Maximum output power800W1600W2400W3200W4000W4800W
Load shunt1 load output
Rated power50Hz
Power factor0.8
Load adjustment rate<2.0%
Frequency accuracy<0.1%
Voltage waveform distortionResistive full load<2%, non-linear full load<5%
Inverter overload
capacity
        1)<100%, continuous operation;     2)100~110%, shut down after 1min;
        3)110~120%, shutdown after 30s
Bypass overload
capacity
        1)<100%, continuous operation;     2)100~110%, shut down after 1min;
        3)110~120%, shutdown after 30s
Efficiency>95%
Solar
charging
mode
PV charging currentNo60A80A
PV voltage rangeNo60~150Vdc
PV maximum open circuit voltageNo145Vdc
Minimum battery voltage for photovoltaic chargingNo34Vdc
Standby power consumptionNo2W
Battery voltage accuracyNo±0.3%
PV voltage accuracyNo±2V
Rated powerNo48V:3000W48V:4000W
Mains modeInput voltage180Vac/260Vac120Vac/230Vac
Lower limit voltageNo95Vac±7V/170Vac±7V(UPS)
65Vac±7V/100Vac±7V(load)
Lower limit recovery voltageNo100Vac±7V/180Vac±7V(UPS)
70Vac±7V/100Vac±7V(load)
Upper limit voltageNo140Vac±7V/280Vac±7V
Upper limit recovery voltageNo135Vac±7V/270Vac±7V
Maximum AC input voltage280Vac150Vac/300Vac
Input frequency47Hz/53Hz50Hz/60Hz(Automatic detection)
Lower limit frequency47±1Hz40±1Hz
Lower limit recovery frequency48±1Hz42±1Hz
Upper limit frequency53±1Hz65±1Hz
Upper limit recovery frequency52±1Hz63±1Hz
Efficiency>92%(rated load, full battery)>95%(rated load, full battery)
Switching time15~20ms10ms(UPS)/20ms(load)
EnvironmentOperating temperature10℃~150℃
Humidity≤95%(non condensing)
CommunicationRS232/RS485RS485Standard configuration: 1-channel
RS232, 2-channel RS485
ProtectionProtection function1. Input under/over voltage, over temperature and output overload protection;
2. Output short circuit protection.
1.Undervoltage/overvoltage protection;   2.Overload protection;
3. High temperature alarm;
4. Soft start.
Mechanical
indicators
W*D*H(mm)482*300*88440*380*130
Weight(KG)7.38.28.59.312.5

1~6KW communication inverter

1) Product introduction:

TXNB series power supply adopts advanced digital control technology, DC current limiting, comprehensive automatic protection, intelligent battery management, unattended, intelligent remote monitoring and other functions, and is a new generation of intelligent power supply system to meet the power supply needs of communication equipment.

2) Application field:

Power plant, substation, dispatching center and workstation.

3) Performance characteristics:

01. Wide input voltage range (AC 185~265Vac).

02. Rack type design, small size and light weight.

03. High efficiency and energy saving. The inverter efficiency can reach more than 93% in the battery state.

04. It is compatible with lithium batteries and can expand 5A, 10A and 60A mains charging functions to meet the needs of different scenarios.

05. Perfect protection functions, including input overvoltage protection, undervoltage protection, battery overvoltage and undervoltage protection, output overvoltage protection, output undervoltage alarm, transfer out short circuit, over temperature and other protection functions.

06. The Chinese display interface is simple to operate and friendly to human-computer interaction. The power system operation and system parameters are clear at a glance.

07. Unattended function. When the mains power is cut off for a long time and the system is automatically protected due to battery undervoltage, it can automatically start up and charge the battery after the mains power returns to normal, effectively protecting the battery and extending the battery life

08. Intelligent communication interface, standard RS232/485 communication interface, can directly and remotely debug and monitor the operation status and parameters of the power supply system through monitoring software, simplifying network management and improving the reliability of the system.

09. Three position dry contact communication interface, mains failure, inverter failure, battery failure (other alarms can be set).